163
EMI
Noise
f
ilter
MC13
-SERIES
Terminal Explanation
Features
(1) 2 mounting options :
MC13** Screw mounting type
MC13**DIN Din rail mounting type
(2) Worldwide compliance :
Voltage rating 3 phase AC500V, 10, 20, 30A
(3) Safe design :
Terminal with cover, Low leakage current
(4) Environmental compliance : Lead free soldering
Safety standard
UL1283
CSA Std. C22. 2 No. 8
EN133200
Circuit
Derating
Request customer specification for further details of specifications, outline, characteristics, etc.
Read the instruction manual before usage.
Contact us about delivery before ordering.
Temperature (C)
Current (%)
EN133200
Specifications
(Note) : Value for Ta
<
50C For Ta>50C derate according to the derating curve shown on the right.
=
Model
STD type
MC1306
MC1310
MC1320
MC1330
Items
DIN type
MC1306DIN
MC1310DIN
MC1320DIN
MC1330DIN
1
Rated Voltage (AC)
500V (50/60Hz)
2
Rated Current (*1)
6A
10A
20A
30A
3
Test Voltage (terminals to base plate, 1min AC)
2000V (100mA) at 25C, 70% RH
4
Isolation Resistance (terminals to base plate, 500VDC)
100M min at 25C, 70% RH
5
Leakage Current
500V,60Hz
5.0mA max
6
DC Resistance (three lines)
90m max
68m max
23m max
11m max
7
Temperature Rise
30C max
8
Operating Temperature
-25C ~ +85C
9
Operating Humidity
30% ~ 95% RH (No Dewdrop)
10
Storage Temperature
-40C ~ +85C
11
Storage Humidity
10% ~ 95% RH (No Dewdrop)
MC13**
At no operating 10~55~10Hz, Amplitude (Sweep for 1min) 0.825mm constant (Maximum 49.0m/s
2
)X,Y,Z 1hour each
12
Vibration
At no operating 55~250~55Hz, Acceleration (Sweep for 1min) 19.6m/s
2
, X,Y,Z 1hour each
MC13**DIN
At no operating 10~55~10Hz, Acceleration (Sweep for 1min) 9.8m/s
2
, X,Y,Z 1hour each
13
Weight
600g
164
EMI
Noise
f
ilter
MC13
-SERIES
MC13
**
DIN
(Unit: mm)
(Unit: mm)
MC13
**
A
B
C
*Mounting
MC13
**
DIN could be mounted on 35mm wide (TS35 type) Din-rail.For mounting,
put the part (A) of the unit over the top hat rail and push forward like (B), so that
the rail stopper is firmly held on the Din-rail. For unmounting, put a screw driver
int the part (C) and lift it up to remove the unit.
*Ground
Do not earth whth Din-rail.
Earth directly from the ground terminal of
MC13
**
DIN.
MC13
**