29
JWS-P
-SERIES
Peak current / Single output 70 ~ 480W
Unit
T
y
pe
Power
S
upply
24V
48V
24V
48V
24V
36V
48V
24V
48V
JWS70P-24
JWS70P-48
JWS120P-24
JWS120P-48
JWS240P-24
JWS240P-36
JWS240P-48
JWS480P-24
JWS480P-48
3.0A
1.5A
5.0A
2.5A
10.0A
6.65A
5.0A
20.0A
10.0A
72W
72W
120W
120W
240W
239.4W
240W
480W
480W
6.0A
3.0A
10.0A
5.0A
20.0A
13.3A
10.0A
40.0A
20.0A
144W
144W
240W
240W
480W
478.8W
480W
960W
960W
JWS70P
JWS120P
JWS240P
JWS480P
Model
Output
Voltage
Average Output
Current
Average Output
Power
Peak output
Current (*1)
Peak output
Power (*1)
1. Input voltage range
2. Power Factor
3. Cooling
4. Operating
Temperature
5. Withstand Voltage
6. Conducted
emission noise
7. Radiated emission
noise
8. PFHC
9. Safety standard
10. Functions
85 ~ 265VAC ( 47 ~ 63Hz) Universal input
0.99 (typ) at 100VAC Average load, 0.92 (typ) at 200VAC Average load
JWS70P, JWS120P: Convection cooling, JWS240P, JWS480P: Forced air by built-in blower
10 ~ +60C (10 ~ +50C: 100%, +60C: 60%)
Input to output: 3kVAC (20mA), Input to FG: 2kVAC (20mA), Output to FG: 500VAC (100mA) for 1 min.
Built to meet EN55011-A, EN55022-A, FCC class A, VCC I class A
Built to meet EN55011-A, EN55022-A, FCC class A, VCC I class A
Built to meet EN61000-3-2
Approved by UL1950 , CSA950 , EN60950 , VDE0160 and UL508 (optional, Note)
OVP, OCP, Thermal protection, JWS240P, JWS480P: Remote ON/OFF control
Model name
JWS120P - 24
Features
marking (Low Voltage Directive)
Applicable to peak output current, compact package
Universal Input (85 ~ 265VAC)
Power Factor & Harmonic Correction (Conform to EN61000-3-2)
EMI (Built to meet EN55011-A, EN55022-A, VCCI-A, FCC-A)
Remote ON/OFF control (JWS240P & JWS480P)
Specifications
Line-up
(*1) Operating time at peak output is less than 10 seconds. (Duty 0.5)
Series name
Average output power
Nominal output voltage
Outline drawing
JWS70P
<
=
(Unit: mm)
(Low Voltage Directive)
3 year warranty
JWS70P JWS120P JWS240P JWS480P
UL
CSA
EN
MAW-1202-22
GO!!
P134
Recommended Noise Filter
Recommended Power Supply Fixture
P198
GO!!
Note: JWS150P 24V output with cover model - UL508 approval is expencted to be confirmed in August 2002
*24V output with cover
: Safety standard approved