ChipFind - документация

Электронный компонент: B44066T0100E690

Скачать:  PDF   ZIP
Thyristor Module TSM-AT

Series/Type: TSM
Ordering code: B44066T0100E690/E525
Date: August
2006
Version: 5
Content of inside pages of data sheet. Data will be automatically entered into frontpage
headlines, headers and footers. Please fill in the table and then change the colour to "White".
This ensures that the table disappears for the customer pdf.
Identification/Classification 1:
(header 1)
Thyristor module for dynamic PFC
Identification/Classification 2:
(header 2)
Accessories for power factor correction
Ordering code:
B44066T0100E690 / B44066T0100E525
Series/Type:
Thyristor module TSM-AT
Preliminary data (optional):
(if necessary)
Preliminary data
Department:
FK PC PM PFC
Date: August
2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
Thyristor module for dynamic PFC B44066T0100E690
/ B44066T0100E525
Accessories for power factor correction
Thyristor module TSM-AT
Preliminary data
Characteristics


Real 3-phase switching
(usage only with single-phase capacitors L-N)
Output up to 120 kVar at 690 V
Usage for PFC-systems with and without
reactors (programmable)
Connected load (output) programmable
Easy programming for the individual
application via multi-lingual plain language
display
Indication of all relevant parameters of the grid
(voltage, current, temperature...)
Alarm output and error message storage



Features
Easy
installation
-
Mechanical assembly directly on a mounting plate
-
Self check after turn-on of main voltage
-
Optimized switching behaviour to the connected load
(tuned/detuned) via the internal processor
-
Storage of optimized parameters for optimum switching
behaviour
Mounting
position
-
Upright; minimum 150 mm space on top and below
Display and control via plain language
graph. Display
- Operation
- Faults
- Activation
Permanent
self-monitoring
- Temperature
- Voltage
- Operating
state








FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 2 of 7
Important notes at the end of this document.
Thyristor module for dynamic PFC B44066T0100E690
/ B44066T0100E525
Accessories for power factor correction
Thyristor module TSM-AT
Preliminary data

Technical data
Voltage
max. 690 V ( 3 x 400 V L-N )
Max
.
power
up to 120 kVar at 690 V
up to 100 kVar at 525 V
Parameter setting via display
nominal voltage, degree of detuning, overcurrent,
alarm temperature, frequency, error message storage,
delay time during cascading
Frequency
50 / 60 Hz
Switching time
Approx. 5 ms
Reset time
Depending on degree of detuning and dimension of
discharge resistor
Ambient operating temperature at nominal load
-10 C ... +55 C
Control features
permanent monitoring of net voltage, phasing,
capacitor current, module temperature. Malfunction
shown in plain language and evaluated; former errors
are stored in an error message storage
Display
3-phase indication of net voltage and capacitor current;
temperature values and all parameters programmed
can be retrieved
Controlling
10-24 V DC , internally DC-insulated; manual operation
possible
Power circuit
connection: three-pole via clamp (50 mm
2
)
Losses P
D
(in W) = 3.0 * I (in A) at 690 V/100 kVar approx.
240 W)
Fuses (mandatory for protection of components)
electronic fuse ,,superfast" 160 A (NH00) for 690 V
electronic fuse "superfast" 200 A (NH1) for 525 V
Dimensions
300 x 300 x 200 mm (w x h x d)
Weight appr.
14
kg
FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 3 of 7
Important notes at the end of this document.
Thyristor module for dynamic PFC B44066T0100E690
/ B44066T0100E525
Accessories for power factor correction
Thyristor module TSM-AT
Preliminary data
Connection diagram: three-phase load (standard)
C3
C2
C1
3x4AT
Control-Input:
1 activation signal - 12V
2 activation signal +12V
3 and 4 alarm output (zero-potential) max 250V,6A
5 and 6 n.c.
Aussc hnitt
65x20 m m
1 2 3 4 5 6 7
L1
L2
L3
N
SL
Thyristor-switch TSM-AT
here: for 690V grid
3xC - star-connection
Fuses for power supply
NH00, superfast
Fuse for
controlvoltage
N
C1
C2
C3
SL
L1
L2
L3
single phase capacitors required






FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 4 of 7
Important notes at the end of this document.
Thyristor module for dynamic PFC B44066T0100E690
/ B44066T0100E525
Accessories for power factor correction
Thyristor module TSM-AT
Preliminary data
Cautions and Warnings
General
Thyristor modules TSM series may only be used for the purpose they have been designed for.
Thyristor modules TSM series may only be used in combination with appropriate pre-switched grid
separator device.
Thyristor modules have to be projected in such a way that in case of any failure no uncontrolled
high current and voltages may occur.
The devices in operation have to be protected against moisture and dust, sufficient cooling has to
be assured.
The connection is made via three phases according to picture 1. Take care for a correct phase
sequence! (If the phase-sequence is not correct, the module will be blocked.)
Activation of the modules is done by a 10 ... 24 V DC signal (by a dynamic reactive power
regulator) which is connected to terminals X3:1 and 2.
For cascading of several modules (for increase of the kVar-output) parallel-connection is possible.
For additional modules, programming of delay time is possible.

The power capacitors are permanently under high voltage (up to 1500 V DC) EVEN IF THE TSM-AT
IS SWITCHED OFF!!
Please follow the instructions:
Due to the switching principle of the thyristor module the power capacitors are permanently loaded to
the peak value of the grid voltage (DC voltage) even when switched off. Therefore following rules
have to be obeyed in any case:
Due to the high voltage (2 x peak value of nominal voltage) that occurs, the discharge resistors of
the power capacitors have to be replaced by special types.
In dynamic systems with TSM modules no fast discharge reactors may be used (reactor would
cause a DC voltage short circuit).
For applications without filter circuit reactors three current limiting reactors are mandatory per
thyristor module.
Thyristor modules in general have to be protected by accordingly dimensioned superfast
electronic fuses.
Those fuses have to be marked in the installation.
Due to the special switching, the PFC capacitors are fully loaded even when the particular step
has been switched off. Protection against contact has to be guaranteed. Warning signals in the
systems are required.
Even in switched off state no electrical isolation is achieved for electronic switches. Therefore
parts of the systems may not be touched after switching off the complete system before the
capacitors have been completely discharged.
Do not touch live parts in the PFC equipment!
Warning signs in the equipment required!
Wait 10 minutes after the main switch is turned off until the voltage in the system is down to an
uncritical value.
FK PC PM PFC
August 2006
Please read Cautions and warnings and
Page 5 of 7