ChipFind - документация

Электронный компонент: G38910120230

Скачать:  PDF   ZIP
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (04.05.2006)
1
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
Product Description
Ordering Key
Type: Dupline
Type no.
Supply
Dupline
Profibus-DP Gateway Passive
Type G 3891 0120
Passive gateway without channel generator
PROFIBUS-DP slave according to EN 50 170
Certified by the PNO
Can be connected at any point in a Dupline
network
Several gateways can be connected to the same
Dupline
network
PROFIBUS-DP communication speed of up to 12 MBaud
Read/control 128 Dupline inputs/outputs through
PROFIBUS-DP
Multiplexed analog signals can be read via the
PROFIBUS-DP network
For mounting on DIN-rail (EN 50 022)
LED indicators for supply, Dupline
carrier and fault
AC power supply
Dupline
Gateway with the
function of a PROFIBUS-DP
slave. This means that the
Dupline
I/O's (incl. multi-
plexed analog signals) can
be read/controlled by
PROFIBUS-DP masters
(PLC's, PC interface cards,
etc. from various suppliers).
Several Dupline
gateways
can be connected to the
same Dupline
network. The
unit is certified by PNO
(Profibus Nutzer Organisa-
tion) which ensures compa-
tibility and interoperability
with other PNO-certified
products.
Supply
Ordering no.
115/230 VAC
G 3891 0120 230
Type Selection
PROFIBUS-DP
RS 485
9-pole female SUB-D
Pin assignment
A
Pin 8
B
Pin 3
RTS
Pin 4
+5V
Pin 6
GND
Pin 5
Baudrate
Auto detection
Cable length
100 m @ 12 MBaud
200 m @ 1.5 MBaud
1200 m @ 93.75 kBaud
Up-date time (128 digital I/O)
Typ. 200 s at 12 MBaud
Typ. 1.6 ms at 1.5 MBaud
Dielectric voltage
PROFIBUS-DP Dupline
4 kVAC (rms)
PROFIBUS-DP ID-no.
6590
GSD-file
G38_120.gsd
Adjustments
2 x 10 pos. rotary switch
PROFIBUS Slave Address
Range 02 to 99
1 x 16 pos. rotary switch
Not used
DIP-switch 1
Not used
DIP-switch 2
Version selection
DIP-switch 3
Not used
DIP-switch 4
Not used
Approvals
PROFIBUS operability
PNO
(Profibus Nutzer Organisation)
Conformity
CE
EMC Industrial Environment
Input/Output Specifications
G 3891 0120 230
Power ON delay
< 2.5 s
Indication for
Supply ON
LED, green
Dupline
carrier
LED, yellow
Fault
LED, red
Environment
Degree of protection
IP 20
Pollution degree
3 (IEC 60664)
Operating temperature
0 to +50C (+32 to +122F)
Storage temperature
-20 to +85C (-4 to +185F)
Humidity (non-condensing)
20 to 80% RH
Mechanical resistance
Shock
15 G (11 ms)
Vibration
2 G (6 to 55 Hz)
Dimensions
H8-housing
Weight
540 g
LED Functions
Red
On DP-Comm
fail
Flash
DP- Device switch in
non-legal position (0,1 or 2)
Off
DP comm Ok
Yellow
On
Dupline carrier Ok
Off
Dupline internal Powerfail
Flashing Dupline Short
Green
ON
Supply is on
OFF
No voltage on the supply
terminals
General Specifications
Du line
Fieldbus
Installationbus
2
Specifications are subject to change without notice (04.05.2006)
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3891 0120
Mode of Operation
The Dupline PROFIBUS-DP
Gateway operates as
a PROFIBUS-DP slave
according to EN 50 170.
This means that the 128
Dupline
I/O's (incl. multi-
plexed analog signals) can
be read/controlled by
PROFIBUS-DP masters like
PLC's and PC interface-
cards from many different
suppliers. Since the
G38910120 is a passive
gateway without channel
generator function, it is pos-
sible to connect several
units to the same Dupline
network. The Dupline
PROFIBUS-DP Gateway is
approved by the PNO
(Profibus Nutzer Organisa-
tion) that ensures compati-
bility with other PNO-certi-
fied products.
Configuration switches
The unit is equipped with
the following switches:
1 x 16-position rotary
switch- not used in the
G38910120.
2 x 10-position rotary
switch for selection of
the PROFIBUS-DP Slave
Address
in the range 02..99.
(00..01 are reserved). Each
module connected to
PROFIBUS-DP must have a
unique slave address which
enables the PROFIBUS-DP
Master to access the
modules individually.
4 x DIPswitches - not used
in the G38910120.
1 x DIP-switch for version
selection
Normally, the version selec-
tion is supposed to be in the
OFF position, especially when
the Gateway is used in new
installations and configured
with the G38_120.GSD file.
In replacements or expansion
of existing installations, this
switch may be switched on,
in order to make set the
Gateway to operate towards
the previous GSD version.
(Mod-6590.GSD)
Dupline Input Data
To ease up the Profibus
Master configuration
, the
G38_120.gsd file is to be
used. This file describes
to the Master which I/O
data the gateway supports.
All I/O data are selectable
through so-called modules,
each described with its par-
ticular function.
Digital Input, Digital output,
Analog input etc. Through
this, the individual con-
figuration of the Gateway is
quite simplified, as the user
only has to select which I/O
modules to use. The
supported modules may be
selected in any order and
any combination.
The G38910120 passive
gateway supports one
Digital input module, and
one Digital output module,
corresponding to the 128
channels of input and out-
put data. Furthermore, the
G38910120 automatically
detects if Multiplexed
analog data are present on
the Dupline. Thus up to 112
Analog values may be read,
and this is done through
additional 14 Input modules,
named "AIn (Mux:CD,0-7)",
"AIn (Mux:CD,8-F)" ... "AIn
(Mux:OP,8-F)".
All modules consist of 16
bytes of data, and the
tables below describe the
content and the relations to
the Dupline data.
If the Dupline signal is
missing or faulty, the gate-
way will set the input status
of all channels to OFF.
Wiring Diagrams
Power supply
230 VAC
Power supply
115 VAC
1
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through term. 21, 22, 23 & 24 See wiring diagram
230
230 VAC 15% (IEC 60038)
115
115 VAC 15% (IEC 60038)
Frequency
45 to 65 Hz
Rated operational power
11 VA
Rated impulse withstand
voltage
230
4 kV
115
2.5 kV
Dielectric voltage
Supply - Dupline
4 kVAC (rms)
Supply - RS 485
4 kVAC (rms)
Du line
Fieldbus
Installationbus
Specifications are subject to change without notice (04.05.2006)
3
Dupline
is a registered trademark. A product of the CARLO GAVAZZI Group
G 3891 0120
Switch Settings
Profibus DP Slave Address
0 0 to 0 1 Reserved
0 2 to 9 9 Legal slave addresses
Pin Assignment
Pin
Signal
3
B
4
RTS
5
GND
6
+5 V
8
A
Dimensions (mm)
H8-housing
Byte 0.. 0F
h
Digital input module
Byte address Dupline Group
Bit
Channel Number
0
A
7
A1
0
A
6
A2
0
A
5
A3
0
.
.
.
0
A
0
A8
1
B
7
B1
2
C
6
C2
.
.
.
.
E
O
1
O7
F
P
0
P8
Byte 0.. 0F
h
Digital output module
Byte address Dupline Group Bit Channel Number
0
A
7
A1
0
A
6
A2
0
A
5
A3
0
.
.
.
0
A
0
A8
1
B
7
B1
2
C
6
C2
.
.
.
.
E
O
1
O7
F
P
0
P8
Byte 0.. 0F
h
Analog input module, multiplexed
Byte address Dupline Groups
multiplex address
0,1 (Hi,Lo)
CD
0
2,3
CD
1
4,5
CD
2
6,7
.
.
A,B
.
.
C,D
CD
6
E,F
CD
7
The multiplexed analog values are represented as
16-bit "sign and magnitude" (2 Bytes: Hi,Lo )
The most significant bit defines the sign (0:+, 1:-) while the
remaining 15 bits define the magnitude (0..32768).
1: Not used
2: Version selection
OFF:
Normal
ON:
Replacement compatible
3: Not used
4: Not used
Not used