1
Class 0.5 (current/voltage)
Universal trasducer: energy, water and gas
32-bit P-based multifunction power transducer
Front size: 90x90 mm
Measurement of single phase and system instantaneous
variables: W, Wdmd, var, var dmd, VA, VA dmd, PF, PF avg,
V
LN
, V
LL
, A
L
, A
n
, Hz, THD (for all measurements max and min
values)
Measured energies: kWh and kvarh on 4 quadrants
Current and voltage inputs with autoranging capability
48 independent energy meters to be used as single,
dual, multi-time energy management
Interface with watt-hour meters by means of digital
inputs (+kWh, +kvarh, -kWh, -kvarh)
Interface with gas and water meters by means of digi-
tal inputs (one water meter, two gas meters to be used
as single or dual time management)
Harmonic distortion analys (FFT) up to the 50th harmonic
(current and voltage)
Harmonics source detection
Optional RS422/485 serial port
Optional RS232 + real time clock function and 2Mb
data logging of alarms, MIN/MAX events and up to 8
variables with programmable time interval.
Product Description
Power quality transducer which
can be used in 3 different oper-
ating modes:
- direct measurements for the
power quality analysis (LV or
MV/HV connection);
- indirect energy and power
measurements by means of
watt-hour meters (LV or MV/HV
connection);
- direct measurements for the
instantaneous variables (LV con-
nection) and indirect measure-
Energy Management
Modular Power Quality Transducer
Type PQT-90
Type selection
Power supply
L:
18 to 60VAC/VDC
H:
90 to 260VAC/VDC
N
No
otte
e:: Slot A + Slot B Max 4
analogue outputs.
Slot C + Slot D max 4 digital
outputs.
1)
On request
Range code (on request)
XXX: None
AV5:
240/415 VAC-
1/5 AAC
(max. 300 V (L-N)/
520 V (L-L) - 6 A)
AV7:
400/690VAC -
1/5 AAC
(max. 480V (L-N) /
830 V (L-L) / 6 A
Slot A (interfacing)
XX:
None
D2:
3 universal digital inputs
+ excitation output
(16-24VDC)
A1:
Single analogue output,
20mADC
1)
A2:
Single analogue output,
5mADC
1)
A3:
Single analogue output,
10mADC
1)
A4:
Single analogue output,
20mADC
1)
Slot A (interfacing cont.)
B1:
Dual analogue output,
20mADC
1)
B2:
Dual analogue output,
5mADC
1)
B3:
Dual analogue output,
10mADC
1)
B4:
Dual analogue output,
20mADC
1)
V1:
Single analogue output,
10VDC
1)
V2:
Single analogue output,
1VDC
1)
V3:
Single analogue output,
5VDC
1)
V4:
Single analogue output,
10VDC
1)
W1:
Dual analogue output,
10VDC
1)
W2:
Dual analogue output,
1VDC
1)
W3:
Dual analogue output,
5VDC
1)
W4:
Dual analogue output,
10VDC
1)
Slot B (communication)
XX:
None
S1:
Serial output,
RS485 multidrop,
bidirectional
B1:
Dual analogue output,
20mADC
1)
B2:
Dual analogue output,
5mADC
1)
B3:
Dual analogue output,
10mADC
1)
B4:
Dual analogue output,
20mADC
1)
W1:
Dual analogue output,
10VDC
1)
W2:
Dual analogue output,
1VDC
1)
W3:
Dual analogue output,
5VDC
1)
W4:
Dual analogue output,
10VDC
1)
Slot C (alarm or pulse)
XX:
None
R1:
Single relay output
(AC1-8AAC, 250VAC)
R2:
Dual relay output,
(AC1-8AAC, 250VAC)
O1:
Single open collector
output (30V/100mADC)
O2:
Dual open collector out-
put (30V/100mADC)
D1:
3 digital inputs for volt-
age-free contacts
D2:
3 universal digital inputs
+ excitation output
(16-24VDC)
Slot D (alarm or pulse)
XX:
None
R2:
Dual relay output,
(AC1-8AAC, 250VAC)
O2:
Dual open collector out-
put (30V/100mADC)
O4:
Four open collector out-
put (30V/100mADC)
Options
X:
None
M:
Serial port RS232+RTC+ 2Mb or Data memory to store all
events, continuous record up to 8 variables and load profile
W
dmd
E1:
WEB-server option
Model
Range code
System
Power supply
Slot A
Slot B
Slot C
Slot D
Options
How to order
PQT-90 AV53H XX XX XX XX X
How to order
PqtSoft Network
PqtSoft Remote
PqtSoft Network: programm to download memory data and
to manage a modem. PqtSoft Remote: programm to set all
the programming parameters.
ments for the energy variables
(LV or MV/HV).
It's possible to add the man-
agement of gas and water
metering to all of these working
modes.
Automatic transmission of SMS
alarm messages.
Remote read-out from GSM
mobile phones of all the instan-
taneous variables, the last vari-
ables available in the data log-
ging and the energy meters.
MODBUS RTU, JBUS protocol
Transmission and reception of SMS messages (vari-
ables and alarm status)
Data transmission and reception by means of analogue modem
Up to 4 optional pulse outputs
Up to 4 optional alarm outputs
Up to 4 optional analogue outputs
Universal power supply: 18-60VAC/VDC, 90-260 VAC/VDC





2
Specifications are subject to change without notice PQT90DS260606
PQT-90
Number of analogue inputs
Current
1 (1-phase; system code: 3)
3 (3-phase; system code: 3)
Voltage
1 (1-phase; system code: 3)
4 (3-phase; system code: 3)
Digital inputs
AQ1038
No. of inputs: 3 (voltage-free)
Purpose
W
dmd
measurement synchro-
nization + var
dmd
and PF
dmd
.
Interfacing with watt-hour meters
(+kWh, +kvarh).
Tariff selection: energy.
Contact measuring current
<8mA/ 17.5 to 25VDC
AQ1042
Number of inputs: 3 +
excitation output
Purpose
W
dmd
measurement synchro-
nization + var
dmd
and PF
dmd
.
Interfacing with watt-hour meters
(-kWh, -kvarh) or/and
measurements of gas /water m
3
.
Tariff selection: energy or GAS.
Excitation output
16V<+Aux<24VDC Max 15mA
Contact measuring current
15mA
Common characteristics
Input frequency
Max 20 Hz, dutycycle 50%
Close contact resistance
Max 1k
Open contact resistance
Min 100k
Insulation
4000VRMS
Max. input number
6 in the configuration:
AQ1038+AQ1042 or 2*AQ1042
Accuracy (display, RS232, RS485)
In: 5A, If.s.: 6A
Un: 240VL-N, Vf.s.: 300VL-N
Current (A
L1
, A
L2
, A
L3
)
0.5% RDG (0.2 to 1.2 In)
(@ 25C 5C, R.H.
60%)
5mA (0.02 to 0.2 In)
Current (A
n
) @ 40 to 100 Hz
1% RDG (0.2 to 1.2 In)
Voltage range AV5:
0,5% RDG (da 48 a 300 V
L-N
)
1% RDG (from 84 to 519V
L-L
)
range AV7:
0,5% RDG (da 80 a 480 V
L-N
)
1% RDG (from 139 to 830V
L-L
)
(@ 25C 5C, R.H.
60%)
Includes also:
frequency, power supply
and output load influences
Frequency
0.1% RDG (40 to 440 Hz)
Active power
(@ 25C 5C, R.H.
60%)
0.5% (RDG + FS) (PF 0.5 L/C,
0.1 to 1.2 In, range AV5) or
1% RDG (PF 0.5 L/C,
0.1 to 1.2 In, range AV5)
Reactive power
(@ 25C 5C, R.H.
60%)
0.5% (RDG + FS) (PF 0.5 L/C,
0.1 to 1.2 In, range AV5) or
1% RDG (PF 0.5 L/C,
0.1 to 1.2 In, range AV5)
Apparent power
(@ 25C 5C, R.H.
60%)
0.5% (RDG + FS)
(0.1 to 1.2 In, range AV5) or
1% RDG
(0.1 to 1.2 In, range AV5)
Energies
(@ 25C 5C, R.H.
60%)
Active: class 1 according to
EN61036
Reactive: class 2 according
to EN61268
Ib: 5A, Imax: 6A
0.1Ib: 500mA,
Start-up current: 20mA
Un: 240V (AV5), 400V (AV7)
Harmonic distortion
1% FS (FS: 100%)
(@ 25C 5C, R.H.
60%)
phase: 2; Imin: 0.1Arms;
Imax: 15Ap; Umin: 50V
RMS
;
Umax: 500Vp
Sampling frequency:
6400 samples/s @ 50Hz
Additional errors
Humidity
0.3% RDG, 60% to 90% R.H.
Input frequency
0.4% RDG, 62 to 400 Hz
Magnetic field
0.5% RDG @ 400 A/m
NOTE: all accuracies are
referred to measurements
carried out with the analogue
input module
Temperature drift
200ppm/C
Sampling rate
6400 samples/s @ 50Hz
Measurements
Current, voltage, power,
energy, power factor, frequen-
cy, harmonic distortion (see
"Display Pages"). TRMS
measurement of a distorted
wave (voltage/current) .
Coupling type
Direct.
Crest factor
3, max. 15Ap/500Vp "AV5"
(L-N), 15Ap/800Vp "AV7" (L-N)
Ranges (impedances)
AV5
58/100 V (> 500 k
) -
1 AAC (
0.3 VA)
58/100 V (> 500 k
) -
5 AAC (
0.3 VA)
240 V/415 V (> 500 k
) -
1 AAC (
0.3 VA)
240 V/415 V (> 500 k
) -
5 AAC (
0.3 VA)
AV7
100/170 V (> 500 k
) -
1 AAC (
0.3 VA)
100/170 V (> 500 k
) -
5 AAC (
0.3 VA)
400/690 V (> 500 k
) -
1 AAC (
0.3 VA)
400/690 V (> 500 k
) -
5 AAC (
0.3 VA)
Frequency
40 to 440 Hz
Overload protection
Continuous: voltage/current:
AV5: 300V
L-N
/ 500V
L-L
/ 6A
AV7: 480V
L-N
/ 830V
L-L
/ 6A
For 1s: voltage/current:
AV5: 600V
L-N
/1040V
L-L
/120A
AV7: 960V
L-N
/1660V
L-L
/120A
Input specifications
0 to 10 mADC,
0 to 5 mADC
0 to 10 VDC,
0 to 10 VDC
0 to 5 VDC
0 to 1 VDC
Analogue outputs (on request)
Number of outputs
Up to 4 (on request)
Accuracy
0.2% f.s.
(@ 25C 5C, R.H.
60%)
Range
0 to 20 mADC,
0 to 20 mADC
Output Specifications
Specifications are subject to change without notice PQT90DS260606
3
PQT-90
Scaling factor
Programmable within the
whole range of retransmis-
sion; it allows the retrans-
mission management of all
values from:
0 to 20 mADC,
0 to 20 mADC
0 to 10 mADC,
0 to 5 mADC
0 to 10 VDC,
0 to 10 VDC
0 to 5 VDC
0 to 1 VDC
Variables to be retransmitted
All (see table"List of the variables
that can be connected to:"...)
Response time
200 ms typical
(filter excluded, FFT excluded)
Ripple
1% according to IEC 60688-1
and EN 60688-1
Temperature drift
200 ppm/C
Load:
20 mA output
600
20 mA output
550
10 mA output
1100
5 mA output
2200
10 V output
10 k
10 V output
10 k
5 V output
10 k
1 V output
10 k
Insulation
By means of optocouplers,
4000V
rms
output to
measuring input
4000V
rms
output to supply input
RS422/RS485
(on request)
Multidrop
bidirectional (static and
dynamic variables)
Connections
2 or 4 wires, max. distance
1200m, termination
directly on the module
Addresses
from 1 to 255, software
programable.
Protocol
MODBUS RTU/JBUS
Data (bidirectional)
Dynamic (reading only)
All variables, see
also the table, "List of the
connected variables".
Static (writing only)
All configuration parameters
energy reset, activation of
digital outputs.
Data format
1 start bit, 8 data bit, no
parity/even parity/
odd parity, 1 stop bit
Baud rate
9600 bit/s
Insulation
By means of optocouplers,
4000 V
RMS
output to
measuring inputs
4000 V
RMS
output to
power supply input
RS232 ((o
on
n rre
eq
qu
ue
es
stt))
Bidirectional (static and
dynamic variables)
Connections
3 wires, max. distance15m
Data format
1 start bit, 8 data bit,
no parity, 1 stop bit
Baud rate
9600, 38400 bit/s
Protocol
MODBUS RTU (JBUS)
Other features
As per RS422/485
Communication by modem
Analogue modem
For the remote communica-
tion of all the data measured
and managed by PQT.
External communication
Modem.
Recommended type: US
Robotics
GSM Modem
For the transmission of
SMS messages:
alarms, instantaneous
variables, last available
variables of data logging
(only average values)
and energy meters.
The alarm messages are
given with the date and the
time of the event. The type
and value of the set-point
can be put into the alarm
message (max 99 charac-
ters). The alarms can also
be transmitted automatically,
while the variables can be
recalled by means of special
SMS question codes.
GSM kit type-tested for PQT
Siemens kit (external)
model "TC35 TERMINAL"
included GSM module,
antenna and 230V power supply.
Digital outputs (on request)
To be used as alarms and/or
retransmission of the
energy metering and/or
outputs remotely
controlled by the serial
communication port.
The outputs are completely
programmable independently of
the type of module being used.
Pulse outputs (on request)
Number of outputs
Up to 4
Type
From 1 to 1000 pulses
programmable for
k-M-G Wh, k-M-G varh,
open collector (NPN transistor)
V
ON
1.2 VDC/ max. 100 mA
V
OFF
30 VDC max.
Outputs connectable to total
and/or partial energy meters
Pulse duration
220 ms (ON),
220 ms (OFF)
According to DIN43864
Insulation
By means of optocouplers,
4000 V
RMS
output to
measuring inputs,
4000 V
RMS
output to
power supply input.
Notes
The outputs can be either open
collector type or relay type
(for the relay output refer to
the specifications described
in the "alarm outputs" section).
Output specifications (cont.)
4
Specifications are subject to change without notice PQT90DS260606
PQT-90
DC 12-5A, 24VDC
AC 15-2.5A, 250VAC
DC 13-2.5A, 24VDC
Min. response time
150 ms, filters excluded,
FFT excluded, setpoint
on-time delay: "0s"
Insulation
4000 V
RMS
output to
measuring input,
4000 V
RMS
output to
power supply input.
Notes
The outputs can be either
relay type or open collector
type (for this latter one, see
the specifications
mentioned in the pulse
outputs)
Alarm outputs (on request)
Number of set-points
Up to 4, independent
Alarm type
Up alarm, down alarm
with or without latch ,
phase asymmetry,
phase loss, neutral loss.
Monitoring of the variable
All the variables listed at
the paragraph "List of the
connectable variables".
Set-point adjustment
0 to 100% of the electrical
scale
Hysteresis
0 to 100% of the electrical
scale
On-time delay
0 to 255 s
Relay status
Selectable: normally
de-energized or normally
energized
Output type
Relay, SPDT
AC 1-8A, 250VAC
Output specifications (cont.)
Software functions
Sampling management
Only for data logger. The
sample stored within the
selected time interval results
from the continuous average
of the measured values. The
average is calculated (min.
sample) with an interval within
two following measurements
of approx. 200 ms.
The variables, up to 8 can be
stored as average value, mini-
mum and maximum instanta-
neos values. Minimum is
intended as lowest value
among those sampled in the
programmed time interval.
Maximum is intended as
highest value among those
sampled in the programmed
time interval.
See "The working mode of
data logging".
Data management type:
FIFO
Memory size
2Mb
Battery life
10 years
Data logger function
The data are stored at time
intervals from 1 to 60 min.; up
to 8 instantaneous variables
can be selected.
Historical data storing time
Two different data logger
function can be selected:
- average calculation within
the programmed time inter-
val.
- Minimum, maximum val-
ues and average calcula-
Operating mode selection
- Direct measurements for
the power quality analysis
(LV or MV/HV connection);
- Indirect energy and power
measurements by means of
watt-hour meters (LV or
MV/HV connection);
- Direct measurements for
the instantaneous variables
(LV connection) and indirect
measurements for the ener-
gy variables (LV or MV/HV).
It's possible to add the
management of gas and
water metering to all of
these working modes.
Pulse weight
Water/gas meter inputs:
selectable from 1 to
10000 pulses/m
3
, energy
from 1 to 10000.00
imp/kWh/kvarh
Transformer ratio
Up to 6000 (CT up to 30kA)
Up to 6000 (VT up to 600kV)
Filters
Filter operating range
0 to 99.9% of the input
electrical scale.
Filtering coefficient
1 to 255
Filter action
Display, alarms, serial outputs
(fundamental variables:
V, A, W and their derived ones).
Event logging
Only with RS232+RTC
module+ Data memory
Type of data
Alarms and max./min. (max.
480 events) stored with date
(dd:mm:yy) and hour
(hh:mm:ss) reference, data
logger.
Specifications are subject to change without notice PQT90DS260606
5
PQT-90
time:
hours, minutes, seconds,
type of stored variable:
variable value.
tion within the pro-
grammed time interval.
See the "Historical data
storing time" table.
Data format
date:
day, month
Software functions (cont.)
PqtSoft Network
English language software
to transfer memory data and
write messages to be
coupled to the SMS alarms,
plus modem
communication
management. The program
runs under Windows
/95/98/98SE/2000/NT/XP.
Working mode
Three different working
modes can be selected:
- management of a local
RS485 network;
- management of modem
communication from a single
instrument to PC (data down-
load);
- management of modem
communication from local
networks (RS485 communi-
cation) to a common PC
(data download).
Data Storing
In pre-formatted XLS files
(Excel data base).
The instantaneous and the
energy, gas, water variables
are stored into two separated
files.
Data Transfer
Manual or automatic at
programmable timings.
Modem communication
Phone book management
(save up to 100 numbers).
Each number is associated to
a modem that corresponds
either to the single instrument
or to a network of instruments.
Each network can manage up to
255 local instruments.
PqtSoft Remote
English language software
to program the working
parameters of the transducer
The program runs under
Windows 95/98/98SE/2000/
NT/XP.
Data access
By means of RS232 serial
port to be coupled to a GSM
or analogue modem or
RS485 port (also multi-drop
availability.).
PqtSoft software: parameter programming and memory data transfer
Product
Energy measurements:
EN61036, EN61268.
Pulse output
DIN43864
Approvals
CE
UL and CSA
Connector
Screw-type
max. 2.5 mm
2
wires (2x 1.5mm
2
)
Housing
Dimensions
90x90x140 mm
Material
ABS,
self-extinguishing: UL 94 V-0
Protection degree
Front: IP20
Weight
Approx. 600 g
(packing included)
Operating
0 to +50C (32 to 122F)
Temperature
(R.H. < 90% non-condensing)
Storage
-10 to +60C (14 to 140F)
temperature
(R.H. < 90% non-condensing)
Insulation reference
voltage
300 V
RMS
to ground (AV5
input)
Insulation
4000 V
RMS
between all inputs/
outputs to ground
Dielectric strength
4000 V
RMS
for 1 minute
Noise Rejection
CMRR
100 dB, 48 to 62 Hz
EMC
EN 50081-2, EN 50082-2
Other standards
Safety
IEC 61010-1, EN 61010-1
General Specifications